A data hall with rows of server cabinets in hot-aisle containment under overhead cable trays

Sector · Data centres

Data Centre Construction in Calgary and Alberta

Server rooms, edge sites and data halls, where the budget and the schedule are set by megawatts, redundancy and the date the power arrives.

Data centre construction in Alberta is planned in megawatts, not square feet. The cost and the schedule are driven by how much power the IT equipment draws, how dense the racks are, and how much redundancy the owner wants in the power and cooling. The building is a shell around a very large electrical and mechanical system. And for most projects, the date the utility can deliver power, and the date the transformers arrive, decide the opening date more than anything the builders do.

Redundancy: Tier I to Tier IV

Data centres are usually described by the Uptime Institute's tier levels, from Tier I, basic capacity with a single path for power and cooling, to Tier IV, fault-tolerant, with fully redundant, independent paths so the site keeps running through a failure of any single component. Each step up adds equipment, space and cost.

The right tier depends on what the data centre does. A company server room or an edge site might need only Tier I or II. A colocation facility or a critical enterprise site usually targets Tier III, where any component can be maintained without shutting down. Agree the target early, because it decides the electrical one-line diagram and the mechanical design.

Power is the critical path

Every megawatt of IT load needs utility power, transformers, switchgear, UPS systems and backup generators, all sized with the redundancy on top. In Alberta, large new loads need a connection agreement with the utility and, depending on size, the transmission system operator. That process can take a long time, and it is often the first thing to start.

A data centre electrical room with switchgear and UPS cabinets
Switchgear, UPS and transformers are long-lead items, ordered long before the building is ready.

The equipment itself has long lead times. Large transformers and medium-voltage switchgear can take many months to manufacture, and ordering them is often the first construction purchase on a data centre, long before the building is ready to receive them.

Cooling

All the power that goes into the IT equipment comes out as heat. Data centres remove it with air-cooled systems, chilled water plants or, for high-density AI and computing racks, liquid cooling direct to the chip or the rack. Alberta's cold, dry climate is an advantage: free cooling with outside air or economizers can carry the load for much of the year, cutting energy use.

Hot-aisle or cold-aisle containment keeps the hot exhaust air from mixing with the cool supply air, and is standard in new halls. Rack density, in kilowatts per rack, decides whether air cooling is enough or liquid cooling is needed.

Backup power

Generators keep the site running through a utility outage, with UPS systems bridging the seconds until the generators start. Diesel generators need fuel storage, enclosures with sound attenuation, and air permits for larger installations. The generator yard, the fuel tanks and the transformer pads take up real site area.

A row of enclosed diesel generators and a pad-mounted transformer beside a data centre
Generators, fuel storage and transformer pads take up a large part of the site.

Fire protection and security

Data halls usually use pre-action sprinklers, which hold water out of the pipes until a fire is detected, sometimes combined with clean agent suppression for critical rooms. Very early smoke detection systems catch overheating equipment before it becomes a fire. Physical security includes perimeter fencing, controlled entry, mantraps and cameras.

Server rooms and edge sites

Not every project is a large data hall. Many Calgary businesses need a dedicated server room in an office or industrial building, with its own cooling, UPS, fire protection and access control. Edge sites, small data centres close to users, are a growing category. These projects follow the same principles at a smaller scale and fit inside an ordinary building, as our office fit-out page explains for the surrounding workspace.

What a data centre costs

MeasurePlanning figure (as of 2026, varies by scope)
Per square foot$650–1,500+
Per megawatt of IT loadabout $12 million

Cost per megawatt is the more useful figure, because the power and cooling systems are most of the cost and they scale with the load, not the floor area. The tier level, the rack density and the cooling approach are what move the number.

Choosing a site

For a data centre, the site is mostly about power. The questions to answer first are how much capacity the local utility can deliver, how soon, and at what voltage. A site next to a substation with spare capacity can save years compared with one that needs new transmission lines. Fibre routes, flood risk, distance from hazards such as rail lines, and room for the generator yard and future expansion come next.

Alberta has attracted interest from large data centre developers because of its power market and climate, and that interest means competition for grid capacity. Start the utility conversation before buying land, and make the purchase conditional on a realistic power timeline where possible.

Building for expansion

Most data centres are built in phases: the shell, the first data hall and the first block of power and cooling, with space and connection points for the next halls. Designing the electrical and mechanical systems so new capacity can be added without shutting down the live halls is one of the most important decisions in the design.

That means leaving space for future switchgear, UPS and chillers, sizing the main electrical and piping routes for the full build-out, and planning the site so new generators and transformers can be installed beside the live ones.

Commissioning

A data centre is not finished when the construction is done. It has to be commissioned: every piece of power and cooling equipment tested on its own, then the whole system tested together under load, including pulling the utility power to prove the UPS and generators carry the site. Load banks simulate the IT equipment so the cooling can be tested before the servers arrive.

Commissioning takes real time and should be in the schedule from the start. It is where problems in the design or the installation are found, and it is far better to find them with load banks than with live servers.

What data centre owners ask us

What tier level do we need?

It depends on how critical the site is. A server room might need Tier I or II. A colocation or critical enterprise site usually targets Tier III, where components can be maintained without shutting down.

What usually decides the schedule?

The utility power connection and long-lead equipment such as transformers and switchgear. Both should be started as early as possible.

Does Alberta's climate help?

Yes. Cold, dry air allows free cooling for much of the year, reducing the energy used for cooling.

Can we build a server room in an existing building?

Usually. It needs dedicated cooling, UPS, appropriate fire protection and access control, and the building's electrical service has to support the load.

Send us the load and the redundancy target

Send the site, the IT load in kilowatts or megawatts, the redundancy level you need and your target date. We will tell you what drives the schedule and give you a planning budget.

Send the load

Or call (403) 273-3202